range of product | Zelio Time | |
product or component type | Modular timing relay | |
discrete output type | Relay | |
width | 17.5 mm | |
device short name | RE17R | |
time delay type | At Di Ht H C Ac A D B Bw |
|
time delay range | 1…10 h 0.1…1 s 6…60 s 10…100 h 6…60 min 1…10 s 1…10 min |
|
nominal output current | 8 A |
contacts type and composition | 1 C/O | |
contacts material | Cadmium free | |
height | 90 mm | |
depth | 72 mm | |
control type | Selector switch front panel | |
[Us] rated supply voltage | 12…240 V AC/DC 50/60 Hz | |
voltage range | 0.85…1.1 Us | |
supply frequency | 50…60 Hz +/- 5 % | |
release of input voltage | 5 V | |
connections – terminals | Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end |
|
tightening torque | 0.6…1 N.m conforming to IEC 60947-1 | |
housing material | Self-extinguishing | |
repeat accuracy | +/- 0.5 % conforming to IEC 61812-1 | |
temperature drift | +/- 0.05 %/°C | |
voltage drift | +/- 0.2 %/V | |
setting accuracy of time delay | +/- 10 % of full scale at 25 °C conforming to IEC 61812-1 | |
control signal pulse width | 100 ms with load in parallel typical 30 ms typical |
|
insulation resistance | 100 MOhm at 500 V DC conforming to IEC 60664-1 | |
reset time | 120 ms on de-energisation typical | |
on-load factor | 100 % | |
power consumption in VA | 0…3 VA at 240 V AC | |
maximum power consumption in W | 1.5 W at 240 V DC | |
minimum switching current | 10 mA at 5 V DC | |
maximum switching current | 8 A AC/DC | |
maximum switching voltage | 250 V AC | |
breaking capacity | 2000 VA | |
operating frequency | 10 Hz | |
electrical durability | 100000 cycles (8 A at 250 V AC maximum) for resistive load | |
mechanical durability | 10000000 cycles | |
dielectric strength | 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1 | |
[Uimp] rated impulse withstand voltage | 5 kV during 1.2/50 µs | |
power on delay | 100 ms | |
marking | CE | |
creepage distance | 4 kV/3 conforming to IEC 60664-1 | |
safety reliability data | MTTFd = 296.8 years B10d = 270000 |
|
mounting position | Any position in relation to normal vertical mounting plane | |
mounting support | 35 mm DIN rail conforming to EN/IEC 60715 | |
local signalling | LED indicator for on steady: relay energised, no timing in progress LED indicator for flashing: timing in progress 80 % ON and 20 % OFF LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF |
|
net weight | 0.07 kg |