Housing | Cylindrical thread design |
Housing | Standard design |
Thread size | M4 x 0.5 |
Diameter | Ø 4 mm |
Sensing range Sn | 0.6 mm |
Safe sensing range Sa | 0.486 mm |
Installation type | Flush |
Switching frequency | 5,000 Hz |
Connection type | Cable, 3-wire, 5 m 1) |
Switching output | PNP |
Output function | NO |
Electrical wiring | DC 3-wire |
Enclosure rating | IP67 2) |
Supply voltage | 10 V DC … 30 V DC |
Ripple | ≤ 20 % 1) |
Voltage drop | ≤ 2 V 2) |
Current consumption | 10 mA 3) |
Time delay before availability | ≤ 10 ms |
Hysteresis | 1 % … 10 % |
Reproducibility | ≤ 2 % 4) |
Temperature drift (of Sr) | ≤ 10 % |
EMC | EN 60947-5-2
IEC 61000-4-2: (Testlevel 2) IEC 61000-4-4: (Testlevel 2) |
Continuous current Ia | ≤ 100 mA |
Cable material | PUR |
Conductor size | 0.06 mm² |
Cable diameter | Ø 2.6 mm |
Short-circuit protection | ✔ |
Reverse polarity protection | ✔ |
Shock and vibration resistance | 30 g, 11 ms / 10 … 55 Hz, 1 mm |
Ambient operating temperature | –25 °C … +70 °C |
Housing material | Stainless steel V2A, DIN 1.4305 / AISI 303 |
Sensing face material | Plastic, POM |
Housing length | 22 mm |
Thread length | 19 mm |
Tightening torque, max. | ≤ 0.8 Nm |
Items supplied | Mounting nut, V2A stainless steel (2x)
Washer, V2A stainless steel, with locking teeth (2x) |
UL File No. | NRKH.E191603 |