Mitsubishi VFDs Inverter 1.5kW FR-A840-00052-2-60
Mitsubishi VFDs Inverter FR-A840 0.4kW to 55kW
Technical Details FR-A840-00023 to -01160
Product line | FR-A840-m-2-60 | ||||||||||||||||
00023 | 00038 | 00052 | 00083 | 00126 | 00170 | 00250 | 00310 | 00380 | 00470 | 00620 | 00770 | 00930 | 01160 | ||||
Output |
Rated motor kW capacity 1 | 120 % overload capacity (SLD) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
150 % overload capacity (LD) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |||
200 % overload capacity (ND) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |||
250 % overload capacity (HD) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | |||
Rated A current |
120 %overload capacity (SLD) | I rated | 2.3 | 3.8 | 5.2 | 8.3 | 12.6 | 17 | 25 | 31 | 38 | 47 | 62 | 77 | 93 | 116 | |
I max. 60 | 2.1 | 4.2 | 5.7 | 9.1 | 13.9 | 18.7 | 27.5 | 34.1 | 41.8 | 51.7 | 68.2 | 84.7 | 102.3 | 127.6 | |||
I max. 3 s | 2.8 | 4.6 | 6.2 | 10.0 | 15.1 | 20.4 | 30.0 | 37.2 | 45.6 | 56.4 | 74.4 | 92.4 | 111.6 | 139.2 | |||
150 %overload capacity (LD) | I rated | 2.1 | 3.5 | 4.8 | 7.6 | 11.5 | 16 | 23 | 29 | 35 | 43 | 57 | 70 | 85 | 106 | ||
I max. 60 | 2.5 | 4.2 | 5.8 | 9.1 | 13.8 | 19.2 | 27.6 | 34.8 | 42.0 | 51.6 | 68.4 | 84.0 | 102.0 | 127.2 | |||
I max. 3 s | 3.2 | 5.3 | 7.2 | 11.4 | 17.3 | 24.0 | 34.5 | 43.5 | 52.5 | 64.5 | 85.5 | 105.0 | 127.5 | 159.0 | |||
200 %overload capacity (ND) | I rated | 1.5 | 2.5 | 4 | 6 | 9 | 12 | 17 | 23 | 31 | 38 | 44 | 57 | 71 | 86 | ||
I max. 60 | 2.3 | 3.8 | 6.0 | 9.0 | 13.5 | 18.0 | 25.5 | 34.5 | 46.5 | 57.0 | 66.0 | 85.5 | 106.5 | 129.0 | |||
I max. 3 s | 3.0 | 5.0 | 8.0 | 12.0 | 18.0 | 24.0 | 34.0 | 46.0 | 62.0 | 76.0 | 88.0 | 114.0 | 142.0 | 172.0 | |||
250 %overload capacity (HD) | I rated | 0.8 | 1.5 | 2.5 | 4 | 6 | 9 | 12 | 17 | 23 | 31 | 38 | 44 | 57 | 71 | ||
I max. 60 | 1.6 | 3.0 | 5.0 | 8.0 | 12.0 | 18.0 | 24.0 | 34.0 | 46.0 | 62.0 | 76.0 | 88.0 | 114.0 | 142.0 | |||
I max. 3 s | 2.0 | 3.8 | 6.3 | 10.0 | 15.0 | 22.5 | 30.0 | 42.5 | 57.5 | 77.5 | 95.0 | 110.0 | 142.5 | 177.5 | |||
Overload capacity 2 | SLD | 110 % of rated motor capacity for 60 s; 120 % for 3 s (max. ambient temperature 40 °C) – inverse time characteristics | |||||||||||||||
LD | 120 % of rated motor capacity for 60 s; 150 % for 3 s (max. ambient temperature 50 °C) – inverse time characteristics | ||||||||||||||||
ND | 150 % of rated motor capacity for 60 s; 200 % for 3 s (max. ambient temperature 50 °C) – inverse time characteristics | ||||||||||||||||
HD | 200 % of rated motor capacity for 60 s; 250 % for 3 s (max. ambient temperature 50 °C) – inverse time characteristics | ||||||||||||||||
Voltage 3 | 3-phase AC, 380–500 V to power supply voltage | ||||||||||||||||
Frequency range | 0.2–590 Hz | ||||||||||||||||
Control method | V/f; advanced magnetic flux vector, real sensorless vector (RSV), closed loop vector, PM sensorless vector control | ||||||||||||||||
Brake transistor 100 % ED | Built-in | ||||||||||||||||
Maximum brake torque | regenerative | 100 % torque/2 % ED with built-in brake resistor | 20 % torque/continuous | ||||||||||||||
with FR-ABR option 7 | 100 % torque/10 %ED | 100 % torque/6 %ED | — | ||||||||||||||
Minimum brake resistance values 6 | Ω | 371 | 236 | 190 | 130 | 83 | 75 | 52 | 34 | 34 | 21 | 21 | 13.5 | 13.5 | 13.5 | ||
Input |
Power supply voltage | 3-phase, 380–500 V AC, -15 %/+10 % | |||||||||||||||
Voltage range | 323–550 V AC at 50/60 Hz (Undervoltage level is selectable by parameter.) | ||||||||||||||||
Power supply frequency | 50/60 Hz ±5 % | ||||||||||||||||
Rated input A current h | SLD | 3.2 | 5.4 | 7.8 | 10.9 | 16.4 | 22.5 | 31.7 | 40.3 | 48.2 | 58.4 | 76.8 | 97.6 | 115 | 141 | ||
LD | 3 | 4.9 | 7.3 | 10.1 | 15.1 | 22.3 | 31 | 38.2 | 44.9 | 53.9 | 75.1 | 89.7 | 106 | 130 | |||
ND | 2.3 | 3.7 | 6.2 | 8.3 | 12.3 | 17.4 | 22.5 | 31 | 40.3 | 48.2 | 56.5 | 75.1 | 91 | 108 | |||
HD | 1.4 | 2.3 | 3.7 | 6.2 | 8.3 | 12.3 | 17.4 | 22.5 | 31 | 40.3 | 48.2 | 56.5 | 75.1 | 91 | |||
Power supply kVA capacity 4 | SLD | 2.5 | 4.1 | 5.9 | 8.3 | 12 | 17 | 24 | 31 | 37 | 44 | 59 | 74 | 88 | 107 | ||
LD | 2.3 | 3.7 | 5.5 | 7.7 | 12 | 17 | 24 | 29 | 34 | 41 | 57 | 68 | 81 | 99 | |||
ND | 1.7 | 2.8 | 4.7 | 6.3 | 9.4 | 13 | 17 | 24 | 31 | 37 | 43 | 57 | 69 | 83 | |||
HD | 1.1 | 1.7 | 2.8 | 4.7 | 6.3 | 9.4 | 13 | 17 | 24 | 31 | 37 | 43 | 57 | 69 | |||
Others |
Cooling | Self cooling | Fan cooling | ||||||||||||||
Protective structure 5 | Enclose type IP20 | Open type (IP00) | |||||||||||||||
Max. heat dissipation i kW | SLD | 0.055 | 0.075 | 0.085 | 0.13 | 0.175 | 0.245 | 0.345 | 0.37 | 0.45 | 0.565 | 0.74 | 0.93 | 1.11 | 1.34 | ||
LD | 0.05 | 0.07 | 0.08 | 0.12 | 0.16 | 0.23 | 0.315 | 0.345 | 0.415 | 0.52 | 0.675 | 0.825 | 1.02 | 1.22 | |||
ND | 0.04 | 0.055 | 0.07 | 0.1 | 0.13 | 0.17 | 0.22 | 0.28 | 0.39 | 0.45 | 0.52 | 0.69 | 0.84 | 1.02 | |||
HD | 0.03 | 0.04 | 0.05 | 0.075 | 0.09 | 0.135 | 0.165 | 0.21 | 0.285 | 0.385 | 0.45 | 0.56 | 0.7 | 0.86 | |||
Weight | kg | 2,8 | 2,8 | 2,8 | 3,3 | 3,3 | 6,7 | 6,7 | 8,3 | 8,3 | 15 | 15 | 23 | 41 | 41 | ||
Dimensions (WxHxD) | mm | 150x260x140 | 220x260x170 | 220x300x190 | 250x400x190 | 325×550 x195 | 435x550x250 |
Order information | Art. no. | 266741 | 266742 | 266743 | 266744 | 266745 | 266746 | 266747 | 266748 | 266749 | 266750 | 266751 | 266752 | 266753 | 266754 |
Remarks:
a The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor. The 200 % overload capacity (ND) is the factory default setting.
b The % value of the overload capacity indicates the ratio of the overload current to the inverter’s rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100 % load.
The waiting periods can be calculated using the r.m.s. current method (I²xt), which requires knowledge of the duty.
c The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the pulse voltage value of the inverter output side voltage remains unchanged at about √2 that of the power supply.
d The rated input capacity varies depending on the impedance values on the power supply side of the inverter (including the cables and input choke).
e FR-DU08: IP40 (except for the PU connector)
f Value for the ND rating
g The braking capability of the inverter can be improved with a optional brake resistor. Please do not use resistor values below the given minimum values.
h The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input choke and cables) affects the rated input current.
i The values displays the maximum possible heat dissipation. Please consider this values during setup of the cabinet. For overseas types refer to page 95.