Mitsubishi VFDs Inverter | FR-CS84 0.4kW to 15kW Three-phase 400 V class | |||||||||
Model FR-CS84-[] | 012 | 022 | 036 | 050 | 080 | 120 | 160 | 230 | 295 | |
Applicable motor capacity (kW) *1 | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | |
Output
Rated capacity (kVA) *2 |
0.9 | 1.7 | 2.7 | 3.8 | 6.1 | 9.1 | 12.2 | 17.5 | 22.5 | |
Rated current (A)*3 |
1.2(1.0) | 2.2(1.9) | 3.6(3.1) | 5.0(4.3) | 8.0(6.8) | 12.0(10.2) | 16.0(13.6) | 23.0(19.6) | 29.5(25.1) | |
Overload current rating *4 | 150% 60 s, 200% 0.5 s (inverse-time characteristics). | |||||||||
Rated voltage *5 | Three-phase 380 to 480 V. | |||||||||
Power supply
Rated input AC voltage/frequency |
Three-phase 380 to 480 V, 50/60 Hz. | |||||||||
Permissible AC voltage fluctuation | 325 to 528 V, 50/60 Hz. | |||||||||
Permissible frequency fluctuation | ±5% | |||||||||
Power supply capacity (kVA) *6 |
1.5 | 2.5 | 4.5 | 5.5 | 9.5 | 12.0 | 17.0 | 20.0 | 28.0 | |
Protective structure (IEC 60529) | Open type (IP20). | |||||||||
Cooling system | Natural. | Forced air. | ||||||||
Approx. mass (kg) | 0.6 | 0.6 | 0.9 | 0.9 | 1.4 | 1.9 | 1.9 | 3.5 | 3.5 | |
Model FR-CS82S-[] | 025 | 042 | 070 | 100 | ||||||
Applicable motor capacity (kW) *1 | 0.4 | 0.75 | 1.5 | 2.2 | ||||||
Rated capacity (kVA) *2 | 1.0 | 1.7 | 2.8 | 4.0 | ||||||
Rated current (A)*3 | 2.5(2.1) | 4.2(3.6) | 7.0(6.0) | 10.0(8.5) | ||||||
Overload current rating *4 | 150% 60 s, 200% 0.5 s (inverse-time characteristics). | |||||||||
Rated voltage *5 | Three-phase 200 to 240 V | |||||||||
Power supply
Rated input AC voltage/frequency |
Single-phase 200 to 240 V, 50/60 Hz | |||||||||
Permissible AC voltage fluctuation | 170 to 264 V, 50/60 Hz | |||||||||
Permissible frequency fluctuation | ±5% | |||||||||
Power supply capacity (kVA) *6 | 1.5 | 2.3 | 4.0 | 5.2 | ||||||
Protective structure (IEC 60529) | Open type (IP20). | |||||||||
Cooling system | Natural. | Forced air. | ||||||||
Approx. mass (kg) | 0.6 | 0.6 | 1.4 | 1.4 |