Contact resistance (see note 2) | 50 mΩ max. |
Operate time (see note 3) | 15 ms max. |
Release time (see note 3) | 15 ms max. |
Max. operating frequency | Mechanical:18,000 operations/hour
Electrical: 1,800 operations/hour (under rated load) |
Insulation resistance (see note 4) | 100 MΩ (at 500 VDC) |
Dielectric strength | Between coil and contacts: 2,000 VAC, 50/60 Hz for 1 minute Between contacts of same polarity: 1,000 VAC, 50/60 Hz for 1 minute |
Vibration resistance | Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude) |
Shock resistance | Malfunction: 200 m/s2 |
Mechanical endurance | 50,000,000 operations |
Electrical endurance (see note 5) | Input:10,000,000 operations (10 mA) or 50,000 operations (1 A) with resistive load 2,500,000 operations (10 mA) or 20,000 operations (1 A) with inductive load Output:1,000,000 operations with rated load |
Error rate (level P) (Reference value) (see note 6) | Input: 100 mA at 1 VDC
Output: 10 mA at 5 VDC |
Ambient temperature | Operating:–40°C to 70°C (with no icing or condensation) |
Ambient humidity | Operating: 5% to 85% (with no icing or condensation) |
Weight | Approx. 17 g |