Item | Specifications |
Model | CS1W-PDC01 |
Applicable PLC | CS-series |
Unit type | CS-series Special I/O Unit |
Mounting position | CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to C200H Expansion I/O Rack or SYSMAC BUS Remote I/O Slave Rack.) |
Maximum number of Units | 80 (within the allowable current consumption and power consumption range) |
Unit numbers | 00 to 95 (Cannot duplicate Special I/O Unit numbers.) |
Special I/O Unit Area |
10 words/Unit
Isolated-type Direct Current Input Unit to CPU Unit: All process values, process value alarms (LL, L, H, HH), rate-of-change values, rate-of-change alarms (L, H), input errors |
DM Area words allocated to Special I/O Units |
100 words/Unit
CPU Unit to Isolated-type Direct Current Input Unit: Input signal type, scaling of process values in industrial units, square root function enable, rate-of-change value range, rate-of-change scaling, number of items for moving average, process value alarm setting (LL, L, H, HH), rate- of-change alarm setting (L, H), zero/span adjustment value, etc. |
Number of inputs | 4 |
Item | Specifications |
Model | CS1W-PDC11 |
Applicable PLC | CS Series |
Unit type | CS-series Special I/O Unit |
Mounting position | CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to C200H Expansion I/O Rack or SYSMAC BUS Remote I/O Slave Rack.) |
Maximum number of Units | 80 (within the allowable current consumption and power consumption range) |
Unit numbers | 00 to 95 (Cannot duplicate Special I/O Unit numbers.) |
Special I/O Unit Area |
10 words/Unit
Isolated-type Direct Current Input Unit to CPU Unit: All process values, process value alarms (LL, L, H, HH), rate-of-change values, rate-of-change alarms (L, H), disconnection alarms, cold junction sensor errors, adjustment period end/notice |
DM Area words allocated to Special I/O Units |
100 words/Unit
CPU Unit to Isolated-type Direct Current Input Unit: Input signal type, scaling of process value in industrial units, process value alarm setting (L, H), inrush input upper limit, inrush input upper limit time, zero/span adjustment value, Square root function. Temperature input signal type, input range (user set), scaling of process value data to be stored in allocated words in CIO area, rate-of-change input range, scaling of rate-of-change data, number of items for moving average, process value alarm setting (LL, L, H, HH), rate-of-change alarm setting (L, H), zero/span adjustment value |
Expansion Control/ Monitor Area |
35 words/Unit
CPU Unit to Isolated-type Direct Current Input Unit: Bits for beginning or resetting the hold function selection, adjustment period control, control bits Isolated-type Direct Current Input Unit to CPU Unit: Adjustment period notices, peak and bottom values, top and valley values, integral values |
Expansion Setting Area |
46 words/Unit
CPU Unit to Isolated-type Direct Current Input Unit: Expansion Setting Area settings, adjustment period control, peak and bottom detection, top and valley detection, integral value calculation |
Number of inputs | 4 |
Input signal type | 4 to 20 mA, 0 to 20 mA, 0 to 10 V, -10 to 10 V, 0 to 5 V, -5 to 5 V, 1 to 5 V, 0 to 1.25 V, -1.25 to 1.25 V (separate for each input), and ±10-V user-set range (specified range within -10.000 V to 10.000 V) |
Scaling | Data to be stored in the allocated words in the CIO area must be scaled (Any minimum and maximum values can be set.) (4 inputs set separately.) Data can be converted at 0% to 100%. |
Data storage in the CIO Area |
The value derived from carrying out the following processing in order of the actual process data in the input range is stored in four digits hexadecimal (binary values) in the allocated words in the CIO Area.
1) Mean value processing ® 2) Scaling ® 3) Zero/span adjustment ® 4) Square root calculation ® 5) Output limits |
Accuracy (25°C) | ±0.05% |