Omron PLC CS-series Process Analog I/O Units CS1W-PTS01-V1

Series#: Omron PLC

Product Details

  • Omron PLC CS-series Process Analog I/O Units CS1W-PTS01-V1
  • Omron PLC Controller Module CP-series
  • We are First Class Omron plc dealer and omron plc distributor in China.
  • We can Supply Omron automation parts,such as Omron PLC,Omron Servo Motor,Omron HMI,Omron VFD and Omron Relay and Omron Sensor and ect.
  • 100% Original and new,In stock by Omron Automation
  • Delivery time: Ready in stock and 1 days for ship out
  • MOQ: 1pcs
Qty:

Specification

Item Specifications
Model number CS1W-PTS01-V1
Applicable PLC CS Series
Unit type CS-series Special I/O Unit
Mounting position CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to C200H Expansion I/O Rack or SYSMAC BUS Remote I/O Slave Rack.)
Maximum number of Units 80 (within the allowable current consumption and power consumption range)
Unit numbers 00 to 95 (Cannot duplicate Special I/O Unit numbers.)
Special I/O Unit Area 10 words/Unit

Thermocouple Input Unit to CPU Unit:

All process values, process value alarms (LL, L, H, HH), rate-of-change values, rate-of-change alarms (L, H), disconnection alarms, cold junction sensor errors

 

DM Area words allocated to Special I/O Units

100 words/Unit

CPU Unit to Thermocouple Input Unit:

Temperature sensor type, input range (user set), scaling of process value data to be stored in allocated words in CIO area, number of items for moving average, process value alarm setting (LL, L, H, HH), rate-of-change alarm setting (L, H), zero/span adjustment value, etc.

Number of temperature sensor inputs 4
 

Temperature sensor types

 

Thermocouple B, E, J, K, N, R, S, T or

-80 to 80 mV. (Set separately for each of four inputs.)

Sensor type, input range, and scaling to industrial units are separate for each of the 4 inputs.

Note: Sensor type, input range, and scaling to industrial units are set in the DM Area.

 

Input ranges

The input range can be set within any of the measurable input ranges shown in Table 1 (below).

Note: Internally, inputs are processed in five ranges (refer to Table 2 below), so accuracy and resolution accord with these internal ranges.

Example:

Thermocouple: K; input range: 0 to 500°C; industrial unit scaling: 0 to 500°C. DM Area settings are as follows: Thermocouple: 3 (0003 hex)

Input signal maximum: 5000 (1388 hex)

Input signal minimum: 0 (0000 hex)

Industrial unit maximum value stored: 500 (01F4 hex) Industrial unit minimum value stored: 0 (0000 hex)

 

Scaling in industrial units

Data to be stored in the allocated words in the CIO area must be scaled (with the minimum and maximum values set). Data can be stored at 0% to 100%.
 

Data storage in the CIO Area

The value derived from carrying out the following processing in order of the actual process data in the input range is stored in four digits hexadecimal (binary values) in the allocated words in the CIO Area.

1) Mean value processing ® 2) Scaling ® 3) Zero/span adjustment ® 4) Output limits