After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

range | TeSys |
product name | TeSys GV3 |
product or component type | Circuit breaker |
device short name | GV3L |
device application | Motor |
poles description | 3P |
network type | AC |
utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 |
network frequency | 50/60 Hz |
breaking capacity | 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz 65 kA Icu at 230/240 V AC 50/60 Hz |
[Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz 60 % at 400/415 V AC 50/60 Hz 60 % at 440 V AC 50/60 Hz |
trip unit technology | Magnetic |
magnetic tripping current | 1120 A |