Article number | 6ES7232-4HA30-0XB0 |
Signal Board SB 1232, 1 AO | |
General information | |
Product type designation | SB 1232, AQ 1×12 bit |
Input current | |
from backplane bus 5 V DC, typ. | 15 mA |
Output voltage | |
Power supply to the transmitters | |
·
● Supply current, max. · |
25 mA |
Power loss | |
Power loss, typ. | 1.5 W |
Analog inputs | |
Number of analog inputs | 0 |
Analog outputs | |
Number of analog outputs | 1 |
Cycle time (all channels) max. | Voltage: 300 μS (R), 750 μS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) |
Output ranges, voltage | |
·
● -10 V to +10 V · |
Yes |
Output ranges, current | |
·
● 0 to 20 mA · |
Yes |
Load impedance (in rated range of output) | |
·
● with voltage outputs, min. · |
1 000 Ω |
·
● with current outputs, max. · |
600 Ω |
Cable length | |
·
● shielded, max. · |
100 m; shielded, twisted pair |
Analog value generation for the outputs | |
Conversion principle | Differential |
Integration and conversion time/resolution per channel | |
·
● Resolution with overrange (bit including sign), max. · |
12 bit |
Errors/accuracies | |
Temperature error (relative to output range), (+/-) | 25 °C ±0.5%, to 55 °C ±1% |
Interrupts/diagnostics/status information | |
Alarms | Yes |
Diagnostics function | Yes |
Diagnostics indication LED | |
·
● for status of the outputs · |
Yes |
Standards, approvals, certificates | |
CE mark | Yes |
CSA approval | Yes |
UL approval | Yes |
cULus | Yes |
FM approval | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
Marine approval | Yes |
Ambient conditions | |
Free fall | |
·
● Fall height, max. · |
0.3 m; five times, in product package |
Ambient temperature during operation | |
·
● min. · |
-20 °C |
·
● max. · |
60 °C |
·
● horizontal installation, min. · |
-20 °C |
·
● horizontal installation, max. · |
60 °C |
·
● vertical installation, min. · |
-20 °C |
·
● vertical installation, max. · |
50 °C |
Ambient temperature during storage/transportation | |
·
● min. · |
-40 °C |
·
● max. · |
70 °C |
Air pressure acc. to IEC 60068-2-13 | |
·
● Storage/transport, min. · |
660 hPa |
·
● Storage/transport, max. · |
1 080 hPa |
Relative humidity | |
·
● Operation at 25 ℃ without condensation, max. · |
95 % |
Pollutant concentrations | |
·
● SO2 at RH < 60% without condensation · |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Mechanics/material | |
Enclosure material (front) | |
·
● Plastic · |
Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 40 g |