Article number | 6ES7332-5RD00-0AB0 |
SIMATIC S7,SM 332 ANALOG OUTPUT | |
Supply voltage | |
Load voltage L+ | |
● Rated value (DC)
|
24 V |
● Reverse polarity protection
|
Yes |
Input current | |
from load voltage L+ (without load), max. | 200 mA |
from backplane bus 5 V DC, max. | 80 mA |
Power loss | |
Power loss, typ. | 4 W |
Analog outputs | |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 70 mA |
Current output, no-load voltage, max. | 14 V |
Output ranges, current | |
● 0 to 20 mA
|
Yes |
● 4 mA to 20 mA
|
Yes |
Load impedance (in rated range of output) | |
● with current outputs, max.
|
500 Ω |
Cable length | |
● shielded, max.
|
200 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max.
|
15 bit |
Errors/accuracies | |
Operational error limit in overall temperature range | |
● Current, relative to output range, (+/-)
|
0.55 % |
Basic error limit (operational limit at 25 °C) | |
● Current, relative to output range, (+/-)
|
0.2 % |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Diagnoses | |
● Overrange
|
Yes |
● Wire-break in actuator cable
|
Yes |
Diagnostics indication LED | |
● Group error SF (red)
|
Yes |
● Channel fault indicator F (red)
|
Yes |
Ex(i) characteristics | |
Module for Ex(i) protection | Yes |
Maximum values of output circuits (per channel) | |
● Co (permissible external capacity), max.
|
850 nF |
● Io (short-circuit current), max.
|
70 mA |
● Lo (permissible external inductivity), max.
|
6.6 mH |
● Po (power of load), max.
|
440 mW |
● Uo (output no-load voltage), max.
|
14 V |
Potential separation | |
Potential separation analog outputs | |
● between the channels
|
Yes |
● between the channels and backplane bus
|
Yes |
● Between the channels and load voltage L+
|
Yes |
Standards, approvals, certificates | |
Use in hazardous areas | |
● Type of protection acc. to EN 50020 (CENELEC)
|
[EEx ib] IIC |
● Type of protection acc. to FM
|
Class I, Division 2, Group A, B, C, D T4 |
● Test number PTB
|
Ex-96.D.2026X |
Ambient conditions | |
Ambient temperature during operation | |
● max.
|
60 °C |
Connection method | |
required front connector | 20-pin |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 120 mm |
Weights | |
Weight, approx. | 280 g |